Fire Plan Review Checklist
Fire Site Plan Review (Fire Department Access)
- Drawings signed and sealed.
- FD access 20' clear width, 13'-6" height.
- Coordination with hydrants and FDC.
- Turnarounds for dead ends 150' or more in length.
- Cul-de-sac min. inside diameter 36' and the min. outside diameter 60'.
- FD access min. right hand turn radius 25'.
- If the building set back more than 150' from the paved FD access, provide a fire lane.
- If the building over 30' in height and setback more than 50' from the paved FD access, provide a fire lane.
- Gates provide sufficient access width (20') and height (13'-6").
- Automatic fence installed on 24-hour occupied structures; optical sensors.
- Fence obstruction to hydrants, hose lay distance, FDC, egress path.